Electrical Specification
Primary Power
120 – 220VAC ± 10%, 60 / 50 Hz. |
Initiating Device CircuitsAll zones are
Class B Style B/C operation (Programmable).
Normal Operating Voltage: 14 – 21 VDC.
Alarm Current: 15 – 30mA.
Short Circuit Current: 45mA Maximum.
Loop resistance: 100 ohms Maximum.
End-Of-Line Resistor: 4K7, 1/2watt
Standby Current: 7mA (2.5mA for Detectors) |
Standby Power
24V D.C
Quiescent current : 120 mA |
|
Operating Condition
Operating Temperature 0 – 49° C/32-120° F.
Relative Humidity 93 ± 2% RH (noncondensing)
at 32 ±2° C/90 ±3° F. |
|
Charging Circuit
Charging Voltage 28.0V, ±0.5V
Charging Current 1.2A(Max) |
Notification Appliance Circuits
Class B Style – Y wiring
Operating Nominal Voltage: 24VDC
Special Application
Current from 12 Zone Upto 64Zone
NACs : 2 Amps (1 A per circuit)
Current above 64Zone
NACs : 4 Amps (1 A per circuit)
Line Drop: 1.8V
End-Of-Line Resistor: 4K7, 1/2watt |
D.C. Output
(Resettable / Steady)
24VDC Output ,1A Max.
Common Relays
Type : Form C
No of Relays : 2
Relay Contact Rating : 2Amps @ 30 VDC,
0.5Amps @ 125VAC.
Power Factor : 1.0 |
|
Dimensions
Zones |
425 |
Height |
Depth |
12 Zone |
425 |
350 |
120 |
16 Zone |
500 |
350 |
120 |
20 Zone |
500 |
600 |
160 |
24 Zone |
500 |
600 |
160 |
32 Zone |
600 |
600 |
160 |
48 Zone |
600 |
700 |
160 |
64 Zone |
600 |
1000 |
160 |
96 Zone |
600 |
1400 |
160 |
128 Zone |
600 |
1400 |
160 |
All dimensions are in mm.
There are no reviews yet.